ASC IHB P Series

Design Features

  • Horizontally mounted design
  • Self cleaning by using backflush principle created by reverse flow
  • Standard sizes from 2” – 24”. Larger sizes available upon request.
  • Available In flanged end connections.
  • Standard thru bolt cover design. Other covers on request
  • Perforated screens are standard.
  • All welders are qualified to ASME Section IX.
  • Strainers designed to meet the requirements of ASME Section VIII,Div.1.
  • Drain with plug is is standard . Drain valves can be supplied on request
  • Vents with plug and Dp indicators are standard
  • Large body with Guaranteed low pressure drop as per Table 3in engineering data .
  • Net free straining area minimum 6 times for standard screen
  • DP Switch are standard. Transmitters can be supplied on request
  • Electrically actuated butterfly backflush valve are standard. Other valves and Pneumatic valves on request
  • Robust bearing design
  • Backflush primemover -3 Phase AC motor 230 volts standard for sizes higher that 25 nb single phase AC motor 230v standard for 25b and lower.
  • Gear box to reduce sppeds to 7 to 14 rpm

Material Data

Body IS1239,3589 ASTM A106, SS304/316, DUPLEX STEEL
Cover A105, SA 516 GR 70, CS TO IS 2062, SS316,304, DUPLEX STEEL
Fastners A193 B7 Bolts & A 194 2 H Nuts with
With spring washer. SS 304/316
Gaskets CAF, NACF, Neoprene, NItrile,PTFE
Drain / Vent Plug A105, CS TO IS 1875-II, Stainless Steel
Filter Element SS 304,316, Duplex, Brass, Monel, Hastalloy C

* Other materials available on request.

Standard Screens

Size Range Opening
2″-8″( 50mm-200mm) 0.125 IN. (3.2mm)
10″-12″(250mm-300mm) 0.125 IN. (3.2mm)
14″-24″(250mm-600mm) 0.188 in. (4.8mm)

Control Panel Specs

IP 65 Double door panel is standard Data Capture
Panel Size : 400 x 400 x300mm Cleaning cycle – Period run
Power supply : 230 Volts 3 phase AC Valve failure report
3 modes viz., Manual,Built in auto and Remote -with 3 point selector swith as standard Olr activated report
Adjustable field setable, Periodic and cyclic timer Debris overload through Dp switch report
Valve Feed Back-Open, close and error Indications
Overload protection for Backflush Motor is standard Power On
RS 485 output for remote data Collection Filteration ON
LCD Display Filter choked
Drain Valve open

Dimensions

Size
mm
A
mm
B
mm
C
mm
50 350 430 1735
80 620 430 2040
100 620 510 2040
150 620 600 2330
200 620 600 2330
250 620 600 2330